SteelMaster 90SB QD logo

ν™”μž¬ λ°©μ§€ λ„λ£Œ

SteelMaster 90SB QD

A one component solventborne acrylic thin film intumescent that provides fire protection for structural steel.

정보 SteelMaster 90SB QD

SteelMaster 90SB QD is one component solventborne acrylic thin film intumescent coating. Independently approved for fire protection of structural steel exposed to cellulosic fire. Can be used as mid coat or finish coat in atmospheric environments. Suitable on approved primers on carbon steel substrates. 

기술 상세 정보

μ œν’ˆ μΉ΄ν…Œκ³ λ¦¬

Fire protection coatings, Building - interior, Intumescent coatings - cellulosic fire, Interior steel protection coatings - buildings

기술

Acrylic

기질

Carbon steel, Steel, Steel roof surfaces

인증 및 승인

EN 13381-8 and EN13381-9
CE marked product with European Technical Assessment ETA 24/0096 
BS 476 part 20/21: Certifire CF 10246 (up to 120 minutes resistance to fire) 
Cellular beams RT1356.β€― 
Reaction to Fire: Class C-s1, d0 (EN 13501-1).β€― 
Durability and Serviceability: Z2, Z1, Y, X (EAD 350402-00-1106) 
ASTM E84: Class A

Declaration of Performance - SteelMaster 90SB QD

 

규격, μΈμ¦μ„œ 및 기타 λ¬Έμ„œμ˜ 더 λ§Žμ€ μ •λ³΄λŠ” TDSλ₯Ό μ°Έμ‘°ν•˜κ±°λ‚˜ ν˜„μ§€ Jotun에 λ¬Έμ˜ν•˜μ‹œκΈ° λ°”λžλ‹ˆλ‹€.

Key features

  • Fire protection from 30 minutes to 120 minutes
  • Majority of steel sections covered
  • Quick drying: 50% faster for dry-to-handle at 5Β°C versus standard version allow for quicker handling and reduced downtime
  • Enhanced safety for construction phase
  • Easy airless spray application
  • Easy to achieve aesthetic finish